FS-I fireproof sealant is a flame retardant, expandable sealant. Its characteristic is the good flame retardancy. When it burns, its volume will expand more than 3 times of its original volume (no constraint), and can effectively prevent flame and heat transferring. This kind of sealant mainly used in all types of cable and other fireproof and sealing parts and systems, such as vertical shaft, dish ark, cable penetration and metal penetration, etc.





Smoke non-toxic;
No halogen, sulfur and other toxic ingredients;
Long-term performance for more than 40 years;
Watertight, smoke airtight;
Resistant to radiation;
Water-based;
No corrosion, safe and environmental protection;
Efficient flame retardant;
Convenient for construction.
Make the penetration holes clean and dry and keep it away from dust and oil stain;
Filling up the holes and gaps with backing materials;
Coating a certain thickness of FS-I in backing material;
Flatting FS-I with tools;
May attach the information card to the wall, so the materials can be identified in later period maintenance.
Test items | Technical specifications | |
1 | Fire Resistance (Fₓₕ) | Fire integrity (E) ≥ 3h, fire insulation (I) ≥ 3h |
2 | Water Flushing Test Performance (C) | No holes causing large-area water leakage after water flushing test post fire resistance |
3 | Combustion Performance | Not lower than Class B2 for building materials specified in GB8624 |
4 | Smoke Toxicity | Not lower than ZA₂ in GB/T20285 |
5 | Air Tightness | ≤3.5m³/(m²·h) |
6 | Apparent Density | ≤2.0×10³kg/m³ |
7 | Compressive Strength | ≥1.0MPa |
8 | Corrosiveness | ≥7 days, no rusting or corrosion |
9 | Water Resistance | ≥3 days, no swelling or cracking |
10 | Oil Resistance | |
11 | Humid Heat Resistance | ≥360h, no cracking or chalking |
12 | Freeze-Thaw Cycle Resistance) | ≥15 cycles, no cracking or chalking |