FB-1 fireproof Cable Coating Board is a kind of high inflation paints fire retardant coating on the surface of non-combustible board. It is mainly applied in sealing the electric cabinet, cable shaft and other large vertical holes.





Smoke non-toxic;
No halogen, sulfur and other toxic ingredients, Long-term performance for more than40 years;
No corrosion, Safe and environmentalprotection;
Efficient flame retardant;
Convenient for construction.
Keep the hole clean and the surface dry;
Cut the FB-1 fireproof sealing plank into the shape that can match the holes and penetrations with tools;
Coat he FS- For FS-I on penetrations surface that is in contact with the sealing plank;
Brush the hole circum and coated board surface on every side with FS- F;
Pull the well-cut sealing plank into the holes, and keep it in a line with the substrate surface, banding with FS-F;
Paint surface of FB-1 with fireproof cable coating.

Test items | Technical specifications | |
1 | Fire Resistance (Fₙₗ) | Fire integrity (E) ≥ 3h, fire insulation (I) ≥ 3h |
2 | Water Flushing Test Performance (C) | No holes causing water flow on the unexposed side after water flushing test post fire resistance |
3 | Combustion Performance | Not lower than Class B₂ for building materials specified in GB8624 |
4 | Smoke Toxicity | Not lower than ZA₂ in GB/T20285 |
5 | Air Tightness | ≤3.5m³/(m²·h) |
6 | Flexural Strength | ≥0.10MPa |
7 | Water Resistance | ≥3 days, no swelling or cracking |
8 | Oil Resistance | |
9 | Humid Heat Resistance | ≥120h, no cracking or chalking |
10 | Freeze-Thaw Cycle Resistance | ≥15 cycles, no cracking or chalking |